Cobra Ridge Runner
Product Information |
Cobra Ridge Runner
Instructions,
Data Sheets, Warranties & Codes |
Cobra® Ridge Runner Exhaust Vent For Roof Ridge
|
Effective attic ventilation is critical for a long-lasting roof!
Cobra® Ridge Runner Exhaust Vent is a key part of the GAF Lifetime
Roofing System, and has even earned the prestigious Good
Homeowner’s Best Choice
|
Professional’s Best Choice
Texas Department of Insurance
|
Balanced Ventilation Requirements
Balanced ventilation requires an equal amount of intake ventilation and exhaust ventilation. GAF recommends, at a minimum, providing 1 square foot of Net Free Ventilation for every 300 square feet of attic floor space. Consult local building codes for specific ventilation requirements in your area.
- Calculate the total square footage of the attic floor area (round up to the next highest number). This number will determine the minimum total linear feet of Cobra® Ridge Runner Exhaust Vent that is needed.
- Find the appropriate amount of Cobra® Ridge Runner Exhaust Vent and minimum intake ventilation that corresponds to the total attic square footage.
|
Based on 1/300 Rule
|
||
|
Total Attic
Square Footage |
Recommended Length of
Cobra® Ridge Runner™ Exhaust Vent (Feet) |
Minimum Intake Ventilation
(Net Free Area in Sq. In.) |
|
1600
|
31
|
388
|
|
1900
|
37
|
463
|
|
2200
|
43
|
533
|
|
2500
|
48
|
600
|
|
2800
|
54
|
675
|
|
3100
|
60
|
750
|
|
3400
|
66
|
825
|
Cobra® Ridge Runner Exhaust Vent has 12.5 sq. in./linear ft. of net free ventilating area.
NOTE: Always have a balanced ventilation system. In no case should the amount of exhaust ventilation at the ridge exceed the amount of soffit ventilation.